Function: 3-point signaller

Settings:

OUT1:

Switch-on point is coupled with the set-point.
Switching difference

Sd1: in units of phys. quantity.

OUT2:

Switch-off point is always below the set-point!
Adjustment range

d.SP : in units of phys. quantity

Switching difference

Sd2: in units of phys. quantity.

Limit value

OUT3:

With the limit value exceeded, the relay is de-energized.
High limit value

H.1: in units of phys. quantity.

Switching difference

HYS.1: in units of phys.quantity.

Signal LEDs:

LED1:

lit, when

OUT1 is energized

LED2:

lit, when

OUT2 is energized

OK LED: lit, when limit value not reached

Parameters:

see chapter 5 “Parameter level”

Configuration level

KS40-1 burner

16

Configuration with

qUIC

HYS.1

Limit

OUT3

OUT2

-X

W

X

W

W

Sd1

Sd2

OUT1

ON

ON

OFF

ON

H.1

OFF

OFF

d.SP