D.1.3, Range, D.1.4 – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 71: Charging the battery, Table 28: sensitivity ranges, D.1.3 range, D.1.4 charging the battery
TM 40/40I, Rev (6) July 2013
Long Range IR3 Fire Simulator
59
4
Wait 20 seconds before repeating the test.
5
Verify that the optical window is clean.
D.1.3 Range
Table 28: Sensitivity Ranges
Sensitivity
Detection
Range (ft. / m)
Standard Test
Range (ft. / m)
Extended Test
Range (ft. / m)
1 (Low)
50 / 15
3.8 / 1.2
7 / 2.2
2
100 / 30
7 /2.2
14.5 / 4.5
3
150 / 45
10 / 3.2
22 / 7
4 (High)
215 / 65
14.5 / 4.5
29 / 9
Notes:
The minimum distance from the detector is 20 inches (50 cm).
The optional beam collimator is fitted for Extended Range.
At extreme temperatures, there is a 15% maximum reduction in the
range.
Important: Keep the Fire Simulator in a safe place when not in use.
D.1.4 Charging the Battery
The Fire Simulator uses NiCd batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates for at least 60
times without recharging. An internal buzzer is sounded when the voltage
from the batteries is lower than the required operational level.
➣
To charge the battery:
1
Place the Fire Simulator on a table in a safe area.
2
Turn the sealed plug (next to the operation button) counter-clockwise
with a suitable wrench.
3
Connect the battery charger.
4
Charge for a maximum of 14 hours.
5
Disconnect the charger.
6
Tighten the sealed plug clockwise.
Warning: Charge the simulator only when the battery is fully discharged.
During activation of the flame simulator, buzzer activation indicates that the