2 automatic bit, Table 10: results of a successful bit, Table 11: results of an unsuccessful bit – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 29
TM 40/40I, Rev (6) July 2013
Internal Detector Tests
17
1.6.2.2 Automatic BIT
The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.
All outputs of BIT results will function as described in Table 10 and Table 11,
and the BIT will be automatically executed every 1 minute.
This continues until a successful BIT occurs, when the detector resumes
normal operation.
Table 10: Results of a Successful BIT
Output
Result
Fault relay
Model 1XXX, 2XXX, 4XXX Wiring options 1, 2, 4:
remains CLOSED
Model 3XXX, 5XXX Wiring options 3 and 5: remains
OPEN
0-20mA
output
Wiring option 1, 2, 3: Normal (4 mA)
Power LED
Green, Flashing, 1 Hz On (Normal)
Table 11: Results of an Unsuccessful BIT
Output
Result
Fault relay
Wiring option 1, 2, 4: changes to Open
Wiring option 3 and 5: changes to Closed
0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED
Yellow, Flashing, 4 Hz
BIT procedure
Performed every 1 minute