beautypg.com

A specifications, Specifications, Technical specifications – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual

Page 55: Aspecifications, A.1 technical specifications

background image

Technical Specifications

43

A

Specifications

In this appendix…

Technical Specifications

page 43

Electrical Specifications

page 44

Outputs

page 44

Approvals

page 46

Mechanical Specifications

page 47

Environmental Specifications

page 47

A.1

Technical Specifications

Spectral Response

Three IR Bands

Detection Range

(at highest Sensitivity
Setting for 1ft

2

(0.1m

2

) pan

fire)

Fuel

ft. / m

Fuel

ft. / m

n-Heptane

215 / 65

Kerosene

150 / 45

Gasoline

215 / 65

Ethanol 95%

135 / 40

Diesel Fuel

150 / 45

Methanol

115 / 35

JP5

150 / 45

IPA (Isopropyl
Alcohol)

135 / 40

Methane*

100 / 30

Polypropylene
Pellets

16 / 5

LPG*

100 / 30

Office Paper

33 / 10

* 20" (0.5m) high, 8" (0.2m) width plume fire

Response Time

Typically 5 seconds

Adjustable Time Delay Up to 30 seconds

Sensitivity Ranges

4 Sensitive ranges for 1 ft

2

(0.1m

2

) n-heptane pan fire from

50 ft. (15m) to 215 ft. (65m)

Fields of View

Horizontal 100

, Vertical 95

Built-In-Test (BIT)

Automatic (and Manual)