1 verifying the detector wiring, Verifying the detector wiring, Table 15: model 40/40i wiring options – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 40: D table 15
SharpEye
TM
IR3 Flame Detector User Guide
28
Connecting the Detector
2.7.1 Verifying the Detector Wiring
The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.
For more information on the wiring options, see Wiring Instructions on
page 49.
For mA wiring options see Figure 10, Figure 11, Figure 12, and Figure 13.
For relay connection options see Figure 9.
Table 15 describes the function of each terminal for all the wiring options.
Table 15: Model 40/40I Wiring Options
Wire
Terminal
No.
Option 1
Default
Option 2
Option 3
Option 4
Option 5
1
+24 VDC
+24 VDC
+24 VDC
+24 VDC
+24 VDC
2
0 VDC
0 VDC
0 VDC
0 VDC
0 VDC
3
Manual
BIT
Manual
BIT
Manual
BIT
Manual
BIT
Manual
BIT
4
Fault
Relay N.C.
Fault
Relay N.C.
Fault
Relay N.O.
Fault
Relay N.C.
Fault
Relay N.O.
5
6
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
Alarm
Relay N.O.
7
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
Alarm
Relay C
8
0-20mA
In
Alarm
Relay N.C.
Alarm
Relay N.C.
Auxiliary
N.O.
Auxiliary
N.O.
9
0-20mA
Out
0-20mA
Out*
0-20mA
Out*
Auxiliary
C
Auxiliary C
10
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
11
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
12
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
*Available with the HART protocol.
Notes:
RS-485 is used for communication network as specified in Appendix C
(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.
Alarm relay:
N.O. energized contact in wiring options 1, 4, 5.
N.O. and N.C. energized in options 2 and 3.