3 other fuels, Table 3: fuel sensitivity ranges – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 21
TM 40/40I, Rev (6) July 2013
Performance Considerations
9
1.5.1.3 Other Fuels
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1ft
2
(0.1m
2
) and is defined as
100% sensitivity.
For fuel fire – standard pan fire size: 1 ft
2
(0.1 m
2
).
For gas flame - 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.
Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Type Of Fuel
Percent of Max. Distance
at each Sensitivity Range
Max. Distance
(ft./m)
Gasoline
100%
215 / 65
N-Heptane
100%
215 / 65
JP5
70%
150 / 45
Kerosene
70%
150 / 45
Diesel Fuel
70%
150 / 45
Ethanol 95%
60%
135 / 40
IPA
60%
135 / 40
Methanol
55%
115 / 35
Methane
45%
100 / 30
LPG
45%
100 / 30
Paper
35%
33 / 10
Polypropylene
15%
16 / 5