TM 40/40I, Rev (6) July 2013

Troubleshooting

45

HART protocol, Fault Relay (N.O), Alarm Relay, (N.O),

(N.C).

Option 3: Power, RS-485, 0-20mA (Source) and
HART protocol, Fault Relay (N.O), Alarm Relay (N.O,

N.C).

Option 4: Power, RS-485, Fault Relay (N.C), Auxiliary

Relay (N.O), Alarm Relay, (N.O).

Option 5: Power, RS-485, Fault Relay (N.O),

Auxiliary Relay (N.O), Alarm Relay, (N.O).

Electrical
Outputs

Dry Contact Relays

Table 22: Contact Ratings

Relay
Name

Type

Normal
Position

Maximum
Ratings

Alarm

SPDT

N.O., N.C.

2A at 30 VDC

Auxiliary

SPST

N.O.

2A at 30 VDC

Fault
(see Notes
1 and 2)

SPST

N.C. or
N.O

2A at 30 VDC

Notes:
1.

The Fault relay (in wiring options 1, 2, 4) is

normally energized closed during normal operation
of the detector. The relay is de-energized open if a

fault condition or low voltage situation.

2.

In wiring options 3, 5 the relay is normally

energized open during normal operation of the
detector. The relay is de-energized close contact if

a fault condition or low voltage situation occurs.

0-20mA Current Output: The 0-20mA can be Sink
or Source according to the wiring option source (see
General Instructions for Electrical Wiring on page 49).
The maximum permitted load resistance is 600Ω.

Table 23: 20 mA Current Output

State

Output

Fault

0 +1 mA

BIT Fault

2 mA±10%

Normal

4 mA±10%

Warning

16 mA±5%

Alarm

20 mA±5%

HART Protocol
The HART protocol is a digital communication signal at
a low level on top of the 0-20mA. This is a bi-
directional field communication protocol used to
communicate between intelligent field instruments