2 troubleshooting, Troubleshooting, Table 20: troubleshooting table – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 51
TM 40/40I, Rev (6) July 2013
Troubleshooting
39
4.2
Troubleshooting
This section is intended to be a guide to correct problems which may happen
during normal operation.
Table 20: Troubleshooting Table
Problem
Cause
Corrective Action
LEDs Off
Fault Relay at N.O
0-20mA at 0mA
No power at the
unit
Check that the correct power
is sent to the detector.
Check power polarity.
Check wiring in the detector.
Send the detector back for
repairs.
Yellow LED flashes
at 4 Hz
Fault Relay at N.O
0-20mA at 0mA
Fault Detector
Low Voltage
Faulty Detector
Check the voltage at the
detector; verify at least 24V
at the detector terminal.
Send the detector back for
repairs.
Yellow LED flashes
at 4 Hz
Fault Relay at N.O
0-20mA at 2mA
BIT Fault
Faulty Detector
Clean detector window.
Re-power the detector.
Replace the detector.
Red LED
constantly on
If no fire exists,
then, detector
alarm latched
Perform Reset to the detector.
Alarm Relay at On
0-20mA at 20mA
Alarm condition
Check cause for alarm.
If no alarm, re-power the
detector.
Send the detector back for
repairs.