4 rs-485 modbus, 5 product certification, 1 atex, iecex – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 18: 2 fm, csa, Rs-485 modbus, Product certification
SharpEye
TM
IR3 Flame Detector User Guide
6
Principles of Operation
Through the HART connection, you are able to perform:
Detector set-up
Detector troubleshooting
Detector health and status
For more details, refer to the HART Manual TM 777030.
1.4.4 RS-485 Modbus
For more advanced communications, the 40/40I detector has an RS 485
Modbus-compatible output that provides data communication from a
network (up to 247 detectors) to a host computer or universal controller for
central monitoring. This feature allows for reduced installation costs, easy
maintenance and local or remote diagnostic tools.
1.4.5 Product Certification
The 40/40I Flame Detectors have the following certifications:
ATEX, IECEx, page 6
SIL-2 Approved, page 7
1.4.5.1 ATEX, IECEx
The 40/40I Flame Detector is certified to:
ATEX Ex II 2 GD per SIRA 07ATEX1250 and IECEx SIR. 07.0085
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
Ex de IIC T4 Ta -55°C to +85°C
Ex tD A21 IP66/X7 T105°C
This product is suitable to use in hazardous zones 1 and 2 with IIC gas
group vapors present.
1.4.5.2 FM, CSA
The 40/40I Flame Detector is certified to FM and CSA Explosion Proof and
Functionality per FM3260:
Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.
Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
Fuel Test Response including: Gasoline, N-Heptane, Diesel, JP5,
Kerosene, Ethyl, Alcohol 95%, IPA, Methanol, Methane, LPG,
Polypropylene, and Paper.