D.1.1, Unpacking, D.1.2 – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 70: Operating instructions, Figure 16: 40/40i ir3 detector target point, D.1.1 unpacking, D.1.2 operating instructions
SharpEye
TM
IR3 Flame Detector User Guide
58
Long Range IR3 Fire Simulator
D.1.1 Unpacking
Verify that you have received the following contents:
Delivery form
Fire Simulator with integral batteries
Battery charger
Optional Beam Collimator
Storage case
D.1.2 Operating Instructions
Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.
Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.
➣
To simulate a fire:
1
Aim the Fire Simulator towards the detector’s Target Point
Figure 16: 40/40I IR3 Detector Target Point
2
When testing keep a distance of at least 50 cm (20 inches) from the
detector.
3
Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).
Target Point