Long Range IR3 Fire Simulator

D.1.1 Unpacking

Verify that you have received the following contents:

Delivery form

Fire Simulator with integral batteries

Battery charger

Optional Beam Collimator

Storage case

D.1.2 Operating Instructions

Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.

Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.

To simulate a fire:

1

Aim the Fire Simulator towards the detector’s Target Point

Figure 16: 40/40I IR3 Detector Target Point

2

When testing keep a distance of at least 50 cm (20 inches) from the
detector.

3

Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).

Target Point