Testing Procedures
➣
To perform Fire Simulator Test:
1
Power up the system and wait up to 60 seconds for the detector to turn
to a normal state. The Power LED turns on.
2
Aim the Spectrex Fire Simulator Model 20/20-310 at the target point of
the detector (Figure 14), in a way that the radiation emitted by it is
facing directly towards the detector. (See Long Range IR3 on page 57).
3
Press the operation button once. After few seconds, a successful test
shows the results shown in Table 19.
Table 19: Results of Successful Fire Simulator Test
Component
Action
Notes
0-20mA
Turn to 20mA
For a few seconds and then return to
4mA
Alarm Relay
Activated
for a few seconds and then returns to
Normal
Auxiliary Relay
Activated
for a few seconds and then returns to
Normal
Fault Relay
Remains active
during the test
LED
Red, steady
The detector is now ready for operation.