IR3 Flame Detector User Guide

46

Approvals

and the host system. HART is available in wiring

options 2 and 3.
Through the HART protocol the detector can:

Display set-up

Reconfigure the set-up

Display detector status and definition

Perform detector diagnostics

Troubleshoot

For more details refer to HART Manual TM777030.

Communication Network: The detector is equipped
with an RS-485 communication link that can be used

in installations with computerized controllers.
The communications protocol is Modbus compatible.

This protocol is a standard and widely used.

It enables continuous communication between a

standard Modbus controller (Master device) and a

serial Network of up to 247 detectors.

Heated
Optics

The front window can be heated to improve performance
in icing, condensation and snow conditions. The heater
increases the temperature of the optical surface by 5-8°F
(3-5°C) above the ambient temperature. The heated
optics can be configured in three ways:

Off: The optics are not heated

On: The optics are heated continuously

Auto: Operated only when the change of temperature
requires the heating. (default)

In Auto mode the start heating temperature can be
defined between 32°F - 122°F (0°C - 50°C). The detector
stops heating the window when the temperature is 27°F

(15°C) above the start temperature.

A.4

Approvals

Hazardous Area
Approvals

FM, CSA
Class I Div. 1 Groups B, C and D;
Class II/III Div. 1 Groups E, F and G.

ATEX, IECEx
Ex II 2 G D
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
or

Ex de IIC T4 Ta -55°C to +85°C
Ex tD A21 IP66/X7 T105°C

Functional

Approvals

EN54-10 approved by VdS

FM approved per FM3260