A.5
Mechanical Specifications
Enclosure
Stainless Steel 316
or
Aluminum, heavy duty copper free (less than 1%),
red epoxy enamel finish
Water and Dust
Tight
NEMA 250 type 6p.
IP 66 and IP 67 per EN 60529
Electronic
Modules
Conformal coated
Electrical
Connection
(two entries)
¾" - 14NPT conduit
or
M25 x 1.5
Dimensions
4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
Weight
Stainless Steel: 6.1 lb. (2.8 kg)
Aluminium: 2.8 lb. (1.3 kg)
A.6
Environmental Specifications
The SharpEye 40/40I is designed to withstand harsh environmental
conditions.
High Temperature
Designed to meet MIL-STD-810C, method
501.1 procedure II
Operating temperature: +167°F (+75 °C)
Storage temperature: +185 °F (+85 °C)
Low Temperature
Designed to meet MIL-STD-810C, method
502.1, procedure I
Operating temperature: -57°F (-50°C)
Storage temperature: -65°F (-55°C)
Humidity
Designed to meet MIL-STD-810C, method
507.1, procedure IV
Relative humidity of up to 95% for the
operational temperature range
Salt Fog
Designed to meet MIL-STD-810C, method
509.1, procedure I
Exposure to a 5% Salt Solution Fog for
48 hours
Dust
Designed to meet MIL-STD-810C, method
510.1, procedure I
Exposure to a dust concentration of 0.3
frames/cubic ft. at a velocity of 1750 fpm, for
12 hours