5 output signals, Output signals, Table 7: available output types – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 25
TM 40/40I, Rev (6) July 2013
Performance Considerations
13
1.5.5 Output Signals
Outputs are available according to the default configuration or the wiring
options selected for the 40/40I detector. Determine the outputs for your
model according to Table 7.
The detector incorporates several types of output suitable to different
control systems:
0-20mA (stepped) with HART
Relays (Alarm, Fault, Auxiliary)
RS-485 Modbus
Table 7: Available Output Types
Output Type
Version
Detector Status
Alarm relay
40/40I – Options 1XXXX,
4XXXX, 5XXXX
The relay is N.O.
40/40I – Options 2XXXX,
3XXXX
The relay is N.O. and N.C.
Auxiliary relay
40/40I – Options 4XXXX
and 5XXXX
The relay is N.O.
Fault relay
40/40I – Options 1XXXX,
2XXXX, 4XXXX
The relay is N.C. energized
40/40I – Options 3XXXX,
5XXXX
The relay is N.O. energized
0-20mA
current output
40/40I – Option 1XXXX
SINK Option, (can be
changed to Source – see
Figure 10, Figure 11 and
Figure 12)
40/40I – Options 2XXXX
and 3XXXX
SOURCE Option with the
HART protocol
RS-485
All versions
Modbus protocol