2 sensitivity ranges, Table 2: sensitivity range levels – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual
Page 20
SharpEye
TM
IR3 Flame Detector User Guide
8
Performance Considerations
1.5.1.2 Sensitivity Ranges
The detector has four user-selectable sensitivity ranges. For each range
there are two response levels.
WARNING (Pre-alarm)
ALARM
The detection distance, for the WARNING level, is approximately 10% higher
than the ALARM distance.
Alarm response times for a standard fire at a specified range are shown
Table 2.
Table 2: Sensitivity Range Levels
Level
Response Time (sec)
Sensitivity Range- ft. (m)
1
3
50 (15)
2 Default
5
100 (30)
3
8
150 (45)
4
10
215 (65)
For some typical ambient conditions the Zeta parameter as defined in NFPA
72 for the detector is 0.005 (1/meter).
Note: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, and so on.