beautypg.com

3 false alarms prevention, False alarms prevention, Table 4: immunity to false alarm sources – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual

Page 23: Table 4

background image

TM 40/40I, Rev (6) July 2013

Performance Considerations

11

1.5.3 False Alarms Prevention

To prevent false alarms, the detector will not alarm or react to the radiation
sources specified in Table 4.

Table 4: Immunity to False Alarm Sources

Radiation Source

Immunity
Distance ft. (m)

Indirect or reflected sunlight

IAD

Vehicle headlights (low beam) conforming to
MS53023-1

IAD

Incandescent frosted glass light, 300 W

IAD

Fluorescent light with white enamel reflector, standard
office or shop, 70 W (or two 35 W)

IAD

Electric arc [12mm (

15

/

32

") gap at 4000 V alternating

current, 60 Hz]

IAD

Arc welding [6 mm (

5

/

16

") rod; 210 A]

See Table 5

Ambient light extremes (darkness to bright light with
snow, water, rain, desert glare and fog)

IAD

Bright colored clothing, including red and safety
orange

IAD

Electronic flash (180 watt-seconds minimum output)

IAD

Movie light, 625 W quartz DWY lamp (Sylvania S.G.-55
or equivalent)

>6.5 (2)

Blue-green dome light conforming to M251073-1

IAD

Flashlight (MX 991/U)

IAD

Radiation heater, 3000 W

>3 (1)

Radiation heater, 1000 W with fan

IAD

Quartz lamp (1000 W)

>3 (1)

Mercury vapor lamp

IAD

Grinding metal

IAD

Lit cigar

>1 (0.3)

Lit cigarette

>1 (0.3)

Match, wood, stick including flare up

>13 (4)

Notes:

IAD = Immune at Any Distance.

All sources are chopped from 0 to 20 Hz.