Series 642

Technical data

Pyromation, Inc.

35

9.0.3

Power supply

Supply voltage

U

b

= 11 to 40 V (8 to 40 V without display), reverse polarity protection

NOTICE

Power supply
► Power must be fed to the device from an 11 to 40 VDC power supply in accordance with NEC

Class 02 (low voltage/current) with short-circuit power limit to 8 A/150 VA.

Residual ripple

Perm. residual ripple U

ss

≤ 3 V at U

b

≥ 13.5 V, f

max.

= 1 kHz

9.0.4

Accuracy

Response time

1 s

Reference operating
conditions

Calibration temperature: +25 °C, ± 5 K; (+77 °F, ± 9 °F)

Maximum measured error

Repeatability

0.03% of the physical input range (15 Bit)
Resolution A/D conversion: 18 Bit

Designation

Accuracy

Digital

D/A

1)

1)

% relates to the set span. Accuracy = digital + D/A accuracy

Resistance thermometer (RTD)

Cu100, Pt100, Ni100, Ni120
Pt500
Cu50, Pt50, Pt1000, Ni1000
Cu10, Pt200

0.2 K (0.36 °F)
0.6 K (1.08 °F)
0.4 K (0.72 °F)
2 K (3.6 °F)

0.02%
0.02%
0.02%
0.02%

Thermocouples (TC)

K, J, T, E, L, U
N, C, D
S, B, R

typ. 0.5 K (0.9 °F)
typ. 1 K (0.18 °F)
typ. 2 K (3.6 °F)

0.02%
0.02%
0.02%

Measuring range

Accuracy

Digital

D/A

1)

1)

% relates to the set span. Accuracy = digital + D/A accuracy

Resistance transmitter (

Ω)

10 to 400

Ω

10 to 2000

Ω

± 0.08

Ω

± 1.6

Ω

0.02%
0.02%

Voltage transmitter (mV)

-20 to 100 mV

± 20

μV

0.02%

Physical input range of the sensors

10 to 400

Ω

Cu10, Cu50, Cu100, polynomial RTD, Pt50, Pt100, Ni100, Ni120

10 to 2000

Ω

Pt200, Pt500, Pt1000, Ni1000

-20 to 100 mV

Thermocouple type: C, D, E, J, K, L, N

-5 to 30 mV

Thermocouple type: B, R, S, T, U