beautypg.com

3 application errors without messages, Application errors without messages, 2 monitoring the supply voltage – Pyromation Series 642 User Manual

Page 30

background image

Trouble-shooting

Series 642

30

Pyromation, Inc.

8.2.2

Monitoring the supply voltage

If the necessary supply voltage is undershot, the analog output value drops approx. 3 s

≤ 3.6 mA.

Error code 19 appears on the display. Then the device attempts to output the normal analog output
value again. If the supply voltage remains too low, the analog output value drops again to

≤ 3.6 mA.

This prevents the device from constantly outputting an incorrect analog output value.

8.3

Application errors without messages

8.3.1

Application errors in general

8.3.2

Application errors for RTD connection

Pt100/Pt500/Pt1000/Ni100

Error pattern

Cause

Action/cure

No communication

No power supply via the
2-wire line

Connect connecting cables correctly in
accordance with terminal plan (polarity)

250

Ω communication resistance missing

See Section 4.3.1 "Connecting HART

®

"

Supply voltage too low (<11 V or 8 V
without display with jumper J3)

Check power supply

Interface cable defective

Check interface cable

Interface defective

Check interface of your PC

Device defective

Replace device

Error pattern

Cause

Action/cure

Error current
(

≤ 3.6 mA or ≥ 21 mA)

Sensor defective

Check sensor

Incorrect RTD connection

Connect connecting cables correctly
(terminal plan)

Incorrect 2-wire line connection

Connect connecting cables correctly in
accordance with terminal plan (polarity)

Faulty device programming (number of
wires)

Change SENSOR CONNECTION device
function

Programming

Incorrect sensor type configured in the
SENSOR TYPE device function; change to
correct sensor type

Device defective

Replace device