Operation

Series 642

14

Pyromation, Inc.

5.2

Local operation

5.2.1

Hardware setting

Fig. 8:

Hardware settings via jumpers J1, J2 and J3

NOTICE

ESD - Electrostatic discharge
► Protect the terminals from electrostatic discharge. Failure to observe this may result in

destruction of parts of the electronics.

Jumpers J1, J2 and J3 for the hardware setting are located at the electronics module. To set the
jumper, open the threaded joint of the electronics module (opposite the threaded joint of the
connection compartment) and remove the display if necessary.

Hardware locking the configuration with jumper J1

The hardware setting for configuration locking has priority over the software setting.

Setting the failsafe mode via the hardware with jumper J2

The failsafe mode set via the jumpers only takes effect if the microcontroller fails.

TRANSMITTER SECURITY

ON

Configuration locked

OFF

Configuration enabled

FAILURE MODE

LO

≤ 3.6 mA

HI

≥ 21.0 mA