Series 642

Trouble-shooting

Pyromation, Inc.

31

8.3.3

Application errors for TC connection

8.4

Return

To reuse later or in case of repair, the device must be packed in protective packaging, preferably the
original packaging. Repairs must only be carried out by your supplier's service organisation or
specially trained personnel.
Enclose a note describing the fault and the application when sending the unit in for repair.

Error pattern

Cause

Action/cure

Measured value is incorrect/
inaccurate

Orientation of the sensor is incorrect

Install sensor properly

Heat conducted by sensor

Observe face-to-face length of the sensor

Faulty device programming (number of
wires)

Change SENSOR CONNECTION device
function

Faulty device programming (scaling)

Change scaling

Incorrect RTD configured

Change SENSOR TYPE device function

Sensor connection (2-wire)

Check sensor connection

Line resistance of sensor (2-wire) was not
compensated

Compensate line resistance

Offset incorrectly configured

Check offset

Error pattern

Cause

Action/cure

Error current
(

≤ 3.6 mA or ≥ 21 mA)

Sensor connected incorrectly

Connect sensor in accordance with
terminal plan (polarity)

Sensor defective

Check sensor

Programming

Incorrect sensor type configured in the
SENSOR TYPE device function; set correct
thermocouple

Device defective

Replace device

Error pattern

Cause

Action/cure

Measured value is incorrect/
inaccurate

Orientation of the sensor is incorrect

Install sensor properly

Heat conducted by sensor

Observe face-to-face length of the sensor

Faulty device programming (scaling)

Change scaling

Wrong thermocouple type (TC) configured Change SENSOR TYPE device function

Incorrect comparison measurement point
configured

See Section "Description of device
functions"

Offset incorrectly configured

Check offset

Interference through thermo-wire welded
in thermowell (interference voltage
coupled in)

Use sensor that does not have a weld-on
thermo-wire