Pyromation Series 642 User Manual
Page 21
Series 642
Commissioning
Pyromation, Inc.
21
Availability in TransComm Light, HART
®
communicator DXR375 (symbol
7
)
TransComm Light
7
Offset
Input of the zero point correction (offset).
Input: -10.00 to 10.00 °C (-18.00 to 18.00 °F)
0.00 °C
+
+
Unit
Display of measurement unit.
Sensor unit = PV unit
+
+
Serial no. sensor
Input of the serial number of the sensor connected to this sensor input.
+
+
Function group SENSOR
Function group OUTPUT
Availability in TransComm Light, HART
®
communicator DXR375 (symbol
7
)
TransComm Light
7
PV lower range value
Input of 4 mA value.
Input: Limitation values see device function SENSOR TYPE.
0 °C
+
+
PV upper range value
Input of 20 mA value.
Input: Limitation values see device function SENSOR TYPE.
100 °C
+
+
Analog output
Input of the standard (4 to 20 mA) or inverse (20 to 4 mA) current output signal.
Input:
• 4 to 20 mA
• 20 to 4 mA
+
+
Filter
Selection of the digital filter 1. order (filter time constant).
Input: 0 to 60 s
+
+
HART Output/
Multidrop
Preamble
Input: Number of response preambles: 5 to 20
5
-
+
Device
address
Input: HART address of the temperature transmitters:
0 to 15
If addresses > 0, the temperature transmitter
is in Multidrop mode and the analogue output is set to 4 mA. Device
address is shown on the display in the Multidrop mode