2 supported hart, Commands – Pyromation Series 642 User Manual
Page 26
Commissioning
Series 642
26
Pyromation, Inc.
6.4.2
Supported HART
®
commands
r = read access, w = write access
• HART
®
command No. 48 (HART-Cmd #48)
Apart from the response code and the device status byte, the field transmitter calls up a detailed
diagnosis by means of Cmd #48. This diagnosis is 8 bytes long.
No.
Description
Access
Universal Commands
00
Read unique identifier
r
01
Read primary variable
r
02
Read p.v. current and percent of range
r
03
Read dynamic variables and p.v. current
r
06
Write polling address
w
11
Read unique identifier associated with tag
r
12
Read message
r
13
Read tag, descriptor, date
r
14
Read primary variable sensor information
r
15
Read primary variable output information
r
16
Read final assembly number
r
17
Write message
w
18
Write tag, descriptor, date
w
19
Write final assembly number
w
Common practice
34
Write primary variable damping value
w
35
Write primary variable range values
w
38
Reset configuration changed flag
w
40
Enter/exit fixed primary variable current mode
w
42
Perform master reset
w
44
Write primary variable units
w
48
Read additional device status
r
59
Write number of response preambles
w
Device specific
144
Read matrix parameter
r
145
Write matrix parameter
w
231
Check Device Status
r