3 user input wiring, 2 input signal wiring, Input a signal wiring – NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual

Page 8: Input b signal wiring

background image

Sinking Logic

Terminal 9:

Terminal 10-11:

}

In this logic, the user inputs of the meter
are internally pulled up to +5 V with 22
K resistance. The input is active when it
is pulled low (<0 .9 V).

3.3 USER INPUT WIRING

Before connecting the wires, the User Input Logic Jumper should be verified for proper position. If not using User

Inputs, then skip this section. Only the appropriate User Input terminal has to be wired.

Sourcing Logic

Terminal 9: -VDC thru external switching device

Terminal 10-11: + VDC thru external switching device

In this logic, the user inputs of the meter are internally
pulled down to 0 V with 22 K resistance. The input is
active when a voltage greater than 3.6 VDC is applied.

Connect external switching device between

appropriate User Input terminal and User Comm.

8

3.2 INPUT SIGNAL WIRING

Current Signal
(self powered)

Terminal 4: -ADC

Terminal 5: +ADC

Voltage Signal

(self powered)

Terminal 4: -VDC

Terminal 5: +VDC

Current Signal (2 wire
requiring excitation)

Terminal 3: +ADC
Terminal 5: -ADC

INPUT A SIGNAL WIRING

Voltage/Current Signal (3 wire requiring excitation)

Terminal 3: +Volt supply
Terminal 4: -ADC (common)
Terminal 5: +ADC (signal)

CAUTION: Sensor Input B common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.

Current Signal
(self powered)

Terminal 7: -ADC

Terminal 8: +ADC

Voltage Signal

(self powered)

Terminal 6: +VDC

Terminal 8: -VDC

Current Signal (2 wire
requiring excitation)

Terminal 6: +ADC
Terminal 8: -ADC

INPUT B SIGNAL WIRING

Voltage/Current Signal (3 wire requiring excitation)

Terminal 6: +Volt supply
Terminal 7: -ADC (common)
Terminal 8: +ADC (signal)

Before connecting signal wires, the Input Range Jumper must be verified for proper position.