6 module 6 - s, None asn-n, No act-n – NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual
Page 19: No spsel, Etpoint, Larm, Arameters, Lit-n, Stb-n, Rst-n
19
5.6 MODULE 6 - S
ETPOINT
(A
LARM
) P
ARAMETERS
(
6-SPt
)
PARAMETER MENU
FLASH
rEv
YES
LAtC2
rEv
0.0
to
3275.0
sec
0.0
to
3275.0
sec
1
to
65000
-19999
to
99999
nor
OFF
LIt-n
- SETPOINT ANNUNCIATORS
NO
Stb-n
- STANDBY OPERATION
LAtC1
AUto
rSt-n
- RESET ACTION
nor
out-n
- OUTPUT LOGIC
tOF-n
- OFF TIME DELAY
tON-n
- ON TIME DELAY
HYS-n
- SETPOINT HYSTERESIS
SP-n
- SETPOINT VALUE
Modules 6, 7, and 8 are accessible only with the appropriate plug-in cards installed. A quick overview of Modules 6 & 8
is listed below. Refer to the corresponding plug-in card bulletin for a more detailed explanation of each parameter selection.
Repeat programming for each setpoint.
Enter the action for the selected setpoint (alarm output).
See Setpoint Alarm Figures in the Setpoint Card Literature for a visual detail
of each action.
NO
= No Setpoint Action
Ab-HI
= Absolute high, with balanced hysteresis
Ab-LO
= Absolute low, with balanced hysteresis
AU-HI
= Absolute high, with unbalanced hysteresis
AU-LO
= Absolute low, with unbalanced hysteresis
dE-HI
= Deviation low, with unbalanced hysteresis
*
dE-LO
= Deviation high, with unbalanced hysteresis
*
bANd
= Outside band, with unbalanced hysteresis
*
bNdIn
= Inside band, with unbalanced hysteresis
*
totLo
= Lower Totalizer absolute high, unbalance hysteresis
**
totHI
= Upper Totalizer absolute high, unbalance hysteresis
**
* Setpoint 2 or Setpoint 4 deviation and band action setpoints are relative to
the value of setpoint 1 or Setpoint 3 respectively. It is not possible to configure
setpoint 1 or 3 as deviation or band actions. It is possible to use setpoint 1 or 3
for an absolute action, while its value is being used for deviation or band.
** These modes only appear, and are the only modes that appear, when the
setpoint assignment
ASN-n
is set to
tot
. The lower Totalizer action,
totLo
,
allows setpoints to function off of the lower 5 digits of the Totalizer. The upper
Totalizer action,
tothI
, allows setpoints to function off of the upper 4 digits
of the Totalizer. To obtain absolute low alarms for the Totalizer, program the
totLo
or
tothI
output logic as reverse.
The parameters listed below are different from those listed in the Setpoint
Card Literature. Use the Refer to Setpoint Option Card Literature for all other
setpoint parameters.
SETPOINT ASSIGNMENT
NONE
ASn-n
NONE
A-rEL A-Abs b-rEL
b-AbS CALC
tot
Selects the meter value that is used to trigger the Setpoint Alarm. The -rEL
settings cause the setpoint to trigger off of the relative (net) input value.
The -AbS settings cause the setpoint to trigger off of the absolute (gross)
input value.
SETPOINT ACTION
NO
ACt-n
NO
Ab-HI
Ab-LO
AU-HI
AU-LO
dE-HI
*
dE-LO
*
bANd
*
bNdIn
totLo
**
tothI
**
SP-4
SP-2
SP-3
SP-1
NO
SPSEL
SELECT SETPOINT
Select a setpoint (alarm output) to open the remaining module menu. (The
“
n
” in the following parameters will reflect the chosen setpoint number.) After
the chosen setpoint is programmed, the display will default to
SPSEL NO
. Select
the next setpoint to be programmed and continue the sequence for each setpoint.
Pressing PAR at
SPSEL NO
will exit Module 6.
NO