KROHNE CORIMASS E Series EN User Manual

Page 88

background image

88

Status messages

ERROR
MESSAGES

TYPE

COMMENT

SAMPLING

Severe

PLL out of range

SENSOR A

Severe

Sensor A voltage signal less than 5% of desired value

SENSOR B

Severe

Sensor B voltage signal less than 5% of desired value

RATIO A/B

Severe

One sensor signal much larger than the other

EEPROM

FATAL

Unable to save data in EEPROM. Hardware fault.

SYSTEM

FATAL

Indicates software error, will always occur with
WATCHDOG

WATCHDOG

Severe

Reset due to SYSTEM error or temporary power supply
drop-off

NVRAM

Severe

NVRAM check sum error, previous data lost

DC A

Severe

DC voltage part of sensor A is larger than 20% of ADC max

DC B

Severe

DC voltage part of sensor B is larger than 20% of ADC max

NVRAM FULL

Light

NVRAM has exceeded its specified number of write cycles

MASS FLOW

Light

Mass flow rate > 2 nominal flow *

ZERO ERROR

Light

Mass flow rate at zero adjust is larger than > 20% of
nominal (100%) flow rate *

TEMPERATUR

Light

Temperature > outside operating range

CURRENT.SAT

Output

Current output saturated **

FREQ.SAT

Output

Frequency output saturated **

ALARM.OUT.A

Output

Process alarm limit check exceeded **

ROM DEF

Light

EEPROM check sum error, defaults loaded from ROM

TOTAL O/F

Light

Custody transfer only. Mass total has overflowed the
display, i.e. it has gone from 99999999 to 00000000

TEMP.CUST

Light

Custody transfer only. Operating temperature has drifted
by more than

±

30

°

C from the zero calibration temperature

POWER.FAIL

Light

Custody transfer only. There has been an interruption of
power to the converter.

*

Actual mass flow rate is too big or manual zero offset SET.VAL in Fct. 1.1.1 or 3.1.1

was

programmed incorrectly.

**

Change output range to avoid saturation.

This manual is related to the following products: