Installation and operating instructions

38 BATCHCONTROL

Object

No

Index

Value (def

ault)

D

esc

ri

pti

on

D

imensi

on

For

mat

min

max

access

Desc

ripto

r

transfe

r

Desc

ript

ion

1 = counter
operates

Bit

1:

Counter

reset

0

=

no

function

1 = reset the
counter

3091H 05H

0

Controlling batching
process

without byte 0

3 w - d

Bit 0: 1 = Start filling through bus,
only at batching process = CAN
Bus (0 = without function)

Bit 1: 1 = Stop filling through bus,
independent from other inputs (0 =
without function)

3091H 06H

0

Learning function

-

byte

0

3

r/w

-

d

Self learning function

Bit

1-0:

Activation

of

function

0

=

function

off

1

=

not

allowed

2 = function on,
no other action

3 = function on
and the next
filling starts the
self learning cycle

3091H 07H

0

Function select for ‘switch
off calculation’

-

byte

0

1

r/w

-

d

Programm select for switch off
calculation
0 = switch off point depends from
the last 1 to 5 tail volumes
1 = switch off point depends from
the actual flow and the last 1 to 5
tail volumes

3091H 08H

0

Function data 1

-

byte

0

5

r/w

-

d

First data for the function ‘switch off
calculation’
Fct = 0: number of tail volumes for
switch off calculation (1 to 5)
Fct = 1: number of tail volumes for
switch off calculation (1 to 5)

3091H 09H

0

Function data 2

-

byte

0

255

r/w

-

d

Second data for the function ‘switch
off calculation’
(for future use)

3091H 0AH 0,001

Volume flow value for
switch off

l/s float

0

15,1

r/w

- d

If the volume flow is lower then this
value, the filling will stop after
number of measurements

3091H 0BH

10

Number of measurements

byte

1

100

r/w

-

d

Parameter for the function 3091.10

3091H 0CH

0 Definition

for

shut-down

without

byte

0

63

r/w

-

d

Bit 0: 1 = output 1 switch off if
3091_05 Bit 1 = 1 , 0 = no
influencing of the output

Bit 1: 1 = output 2 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output

Bit 2: 1 = output 3 switch off if
3091_05 Bit 1 = 1 , 0 = no
influencing of the output

Bit 3: 1 = output 4 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output

Bit 4: 1 = output 5 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output

Bit 5: 1 = output 6 switch off if
3091_05 Bit 1 = 1, 0 = no
influencing of the output

3091H 0DH

100 Fixed tail volume 1

ml

byte

0

255

r/w

-

d

this tail volume is used for the next
filling (if the bit 4 is set in RPDO1)
and after power on

3091H 0EH

100 Fixed tail volume 2

ml

byte

0

255

r/w

-

d

this tail volume is used for the next
filling (if the bit 5 is set in RPDO1)

3091H 0FH 10

Percentage of target
volume

% byte

0 50

r/w

- d

this tail volume is used for the next
filling (if the bit 6 is set in RPDO1)

3092H Status values and PDO definition

3092H 00H

2

Number of entries

without

byte

-

-

r

-

d

3092H 01H

0

Actual status of batching without

byte

0 5 r

91H

-

Bit

0-3:

actual

status

of

batching

0

=

stop