KROHNE BATCHCONTROL 5014 C User Manual
Page 31
Installation and operating instructions
BATCHCONTROL
Object
No
Index
Value (def
ault)
D
esc
ri
pti
on
D
imensi
on
For
mat
min
max
access
Desc
ripto
r
transfe
r
Desc
ript
ion
1 = no message
output
0 = activation of
message output
3002H 03H 0,0
Volume flow with time
constant
l/s float
-15,1
15,1
r
02H
-
actual measurement flow value with
time constant
3002H 04H
4
Sending function for Index
03H
without byte 0
4 r/w - d
Sending function Measurement
value with time constant
Bit
1-0:
Priority
00
=
PDO
0
01
=
PDO
1
10
=
PDO
2
11
=
PDO
3
Bit
2:
activation
of
function
1 = no message
output
0 = activation of
message output
3002H 05H
0,0
Currently measured volume
l
float -1000 1000 r 03H d Currently
totalized
volume
3002H 06H
4
Sending function for Index
05H
without byte 0
4 r/w - d
Bit 2-0: Sending function volume
counter
Bit
1-0:
Priority
00
=
PDO
0
01
=
PDO
1
10
=
PDO
2
11
=
PDO
3
Bit
2:
activation
of
function
1 = no message
output
0 = activation of
message output
3003H Alarm values and PDO definition
3003H
00H
8
Number
of
entries
without
byte - - r - -
3003H 01H
1
Maximum volume flow l/s
float
0,0001
15,1
r/w
-
d
Limit value for volume flow (without
time constant) with emergency
shut-down
3003H 02H
0 Definition
for
shut-down
without
byte
0
63
r/w
-
d
Bit 0: 1 = output 1 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 1: 1 = output 2 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 2: 1 = output 3 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 3: 1 = output 4 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 4: 1 = output 5 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 5: 1 = output 6 switch off if
volume flow is to high, 0 = no
influencing of the output
3003H 03H
- Actual
status
without byte 0
1 r 04H -
Bit 0: 1 = Limit value exceeded, 0 =
okay
3003H 04H
4
Sending function for Index
03H
without byte 0
4 r/w - d
Bit
1-0:
Priority
00
=
PDO
0
01
=
PDO
1
10
=
PDO
2
11
=
PDO
3
Bit
2:
activation
of
function
1 = no message
output
0 = activation of
message output
3003H 05H 1,0 Maximum
volume
l
float 0,0001 100,0
r/w
-
d
Limit value for counted volume with
emergency shut-down
3003H 06H
0 Definition
for
shut-down
without
byte
0
63
r/w
-
d
Bit 0: 1 = output 1 switch off if