Installation and operating instructions

23

BATCHCONTROL


6.3 Signal

converter


Power supply

Voltage

24 V DC, ± 20%

Power consumption

≤ 5 W excl. external loads

Electrical connection

two M12 plug-in connector

Operator control

All operating data factory-set to your specifications.

Available as option for change of operating data:

- KROHNE software for operator control via PC.

Options connected to the CAN bus interface

6 Valve outputs

low or high side activ

Function

programmable to control valves,

short and cable broken detect

Voltage

24 V DC, ± 20%

Load rating

I

max

≤ 200 mA

Load short

I

short

≤ 2 A

6 Analogue inputs

alternative to the outputs

Function

programmable for alarm messages,

to control the filling process

Voltage

0 – 11 V DC, resolution of 8 bit

Impedance

input 1 and 2:

220 kOhm

Input 3 to 6:

22 kOhm

Electronic temperature sensor

Function

programmable for alarm messages

Range

-20°C … +100°C

Error

± 3 K

Fluid temperature sensor

Function

programmable for alarm messages

Range

-20°C … +140°C

Error

± 3 K

CAN bus

Baud rate

20k … 1M baud

6