Installation and operating instructions

30 BATCHCONTROL


E 2

CAN parameter

Object

No

Index

Value (def

ault)

D

esc

ri

pti

on

D

imensi

on

For

mat

min

max

access

Desc

ripto

r

transfe

r

Desc

ript

ion

10xxH CANopen parameter

1000H 00H

Device type

without

long

0

r

-

-

0x00000014 (const. value)

1008H 00H

Manufacturer Device Name

without

string

- - r - -

“IFC

1009H 00H

Manufacturer Hardware
Version

without

string

- - r - -

“014

1010H Parameter save

1010H

00H

1

Number

of

entries

without

byte - - r - -

1010H 01H

Save all parameters in
EEPROM

without long - - r/w - d

Save databytes: 65H 76H 61H 73H
Read: 00H 00H 00H 01H

1011H Parameter recall

1011H

00H

1

Number

of

entries

without

byte - - r - -

1011H 01H

1

Recall all parameters from
EEPROM to RAM

without long - - r/w - d

Recall databytes: 64H 61H 6FH
6CH
Read: 00H 00H 00H 01H

1017H 00H

250 Consumer heartbeat time

ms

word

0

65535

r/w

-

d

1018H Identity Object

1018H

00H

4

Number

of

entries

without

byte - - r - -

1018H

01H

Vendor

Id

without

long - - r - -

1018H

02H

Product

code

without

long - - r - -

1018H

03H

Revisionsnumber

without

long - - r - -

1018H

04H

Serialnumber

without

long - - r - -




300xH Flow sensor parameter

3001H Sensor parameter

3001H

00H

7

Number

of

entries

without

byte - - r - -

3001H 01H

1

Full scale range

l/s float

0,0015

15,1

r/w

- d

Full scale value, basis for values
given as percentage values

3001H 02H

1 Time

constant

S

float 0,1 99 r/w - as

Time constant for output value, of
no significance for
BATCHCONTROL

3001H 03H 15 Meter

size

mm

float

2,5

40

r/w

-

as

Meter size of tube

3001H 04H 3,3 Sensor

constant

without float 0,5 9,9 r/w

-

as

Calibration constant of Sensor

3001H 05H

0

Zero point

l/s

float

-1,0

+1,0

r/w

-

as

Zero point of Sensor

3001H 06H

0 Flow

direction

without byte 0

1 r/w - as

0 = as printed on
instrument

1 = contrary to
imprint

3001H 07H

0

Auto zero function

-

byte

0

1

r/w

-

d

Zero point calculation

Bit

0:

Activation

of

function

1 = function
active

0 = function
switched off

3002H Measurement values and PDO definition

3002H

00H

6

Number

of

entries

without

byte - - r - -

3002H 01H 0,0

Volume flow without time
constant

l/s float

-15,1

15,1

r

01H

-

Actual measurement flow value
without time constant

3002H 02H

4

Sending function for Index
01H

without byte 0

4 r/w - d

Sending function measurement
value without time constant

Bit

1-0:

Priority

00

=

PDO

0

01

=

PDO

1

10

=

PDO

2

11

=

PDO

3

Bit

2:

Activation

of

function

E