Installation and operating instructions

13

BATCHCONTROL

2 Electrical

connection

2.1 Important

information

Be sure to take note of the following
information in order to ensure proper
functioning of the signal converter.

Please note:
1) Overvoltage class:

In conformity with VDE 0120, equivalent
to IEC 664, the compact flowmeters are
designed for overvoltage category III in
the supply circuits and overvoltage
category II in the output circuits.

2) Safety isolation:

The compact flowmeters must be
provided with an isolating facility.

Electrical connection and repairs may only
be carried out by qualified personnel.

Protect the flowmeter from direct radiant
heat
(e.g. hot-product tanks), insulate if
necessary.

Do not expose flowmeter to intense
vibration. If necessary, support the
pipeline to the right and left of the
flowmeter. Level of vibration in accordance
with IEC 068-2-34: below 2.2g in the 20 -
2000 Hz frequency range.

Note information given on the instrument
nameplate
, voltage.

The FE functional ground for the supply
power should for measurement reasons be
connected to the separate U-clamp
terminal on the signal converter housing.

When connected to a functional extra-
low voltage of 24 V DC,
protective
separation (PELV) must be ensured (VDE
0100 / VDE 0106 or IEC 364 / IEC 536 or
equivalent national regulations)..


2.2 Attachment plugs

Manufacturer Series and type Description

Binder

Series 715

Moulded plug, straight or
angle-entry form

Series 763

Integrally extruded plug
with cable in various
lengths

Hirschmann E-Series

ELKA 4012 and
ELWIKA 4012

Moulded plug, straight or
angle-entry form

ELKA KV 4412
and ELWIKA KV
4412

Integrally extruded plug
with cable in various
lengths

Lumberg RK-Series

RKC and RKCW Moulded plug, straight or

angle-entry form

RKT and RKWG

Integrally extruded plug
with cable in various
lengths

Amphenol

Series C 164 P

Moulded plug, straight or
angle-entry form

Series C 164 P
compact

Integrally extruded plug
with cable in various
lengths

Coninvers

Series BC

Moulded plug, straight
form, especially suitable
for high-interference
environments (keyword:
EMC)

Pin-assignment and
alignment of cable entry
body