Installation and operating instructions

18 BATCHCONTROL

volume.

Output ‘3’ is used for the carbonizing of the bottle. This valve ist used at the beginning of

the filling process. It opens for 0,6 second.

Output ‘4’ is used for unpreasurizing the bottle at the end of the filling process. It opens for

1 second.

Output ‘5’ an ‘6’ are not used.

CAN PARAMETER

Letter Object

No.

Description

output 1

3031.01

Function of the block

3034.01

Output hardware function

output 2

3041.01

Function of the block

3044.01

Output hardware function

output 3

3051.01

Function of the block

3054.01

Output hardware function

output 4

3061.01

Function of the block

3064.01

Output hardware function

output 5

3071.01

Function of the block

output 6

3081.01

Function of the block


The following graphic shows the timing diagram of the filling process.

time parameter

-0,02

0,00

0,02

0,04

0,06

0,08

0,10

0,12

0,14

0,16

0,00

2,00

4,00

6,00

8,00

10,00

12,00

14,00

16,00

18,00

t[s]

Q[l/s]

A B

C D

E F G H I

J

output 1

output 2

output 3

output 4

At the time of ‘A’ the filling starts. The bottle gets pressurized with CO2 (‘B’ – ‘C’). After this both
product valves opens at the time of 'D'. The high speed valve is closed after 950ml (‘E’) is filled.
The low speed valve is closed at the time of 'F' and the filling is completed to 'G'. The last step is to
depressurize the bottle ('H' – ‘I’). The next filling starts after 'J'.

CAN PARAMETER

Letter Object

No.

Description

A

3091.05

Controlling batching process

B

3054.02

Output 3 on function definition

3054.03

On value (output 3)

C

3054.05

Output 3 off function definition

3054.06

Off value (output 3)

D

3091.02

Forward run time

3034.02

Output 1 on function definition

3044.02

Output 2 on function definition

E

3044.05

Output 2 off function definition

3044.06

Off value (output 2)

F

3034.05

Output 1 off function definition

G

3091.07

Function select ‘switch off calculation’

3091.08

Function

data

1

3091.0A

Volume flow value for switch off

3091.0B

Number of measurements

3091.0C

Definition for shut-down

4