1. Referenced Documents
HART Physical Layer Specification - Revision 7.0
D8900097
HART Data Link Layer Specification - Revision 7.0
D8900098
HART Command Summary Information - Revision 7.0
D9000048
HART Universal Command Specification - Revision 5.1
D8900038
HART Common-Practice Command Specification - Revision 7.0
D9000050
HART Common Tables - Revision 5.0
D9000051
2. Expanded Device Type Code
Manufacturer Identification Code
= 69
(0x45)
Manufacturer¥s Device Type Code
= 246 (0xF6)
The merger of these two 8-bit codes forms the 16-bit Expanded Device Type Code.
Expanded Device Type Code = 17910
3. IFC010 Conformance And Command Class Summary
Command
Description
Number
CONFORMANCE CLASS #1
- UNIVERSAL
0
Read Unique Identifier
1
Read Primary Variable
CONFORMANCE CLASS #1A
- UNIVERSAL
0
Read Unique Identifier
2
Read Primary Variable Current and Percent of Range
CONFORMANCE CLASS #2
- UNIVERSAL
11
Read Unique Identifier Associated with Tag
12
Read Message
13
Read Tag, Descriptor, Date
14
Read Primary Variable Sensor Information
15
Read Primary Variable Output Information
16
Read Final Assembly Number
CONFORMANCE CLASS #3
- UNIVERSAL
3
Read Dynamic Variables and P.V. Current
- COMMON-PRACTICE
33
Read Transmitter Variables
48
Read Additional Transmitter Status
50
Read Dynamic Variable Assignments
60
Read Analog Output and Percent of Range
62
Read Analog Outputs
- TRANSMITTER-SPECIFIC
128
Read Hardware Information
129
Read Device Implementation Code
130