KROHNE IFC 010 Converter HART User Manual
Page 23
HARTÆ Communications Protocol
IFC010 Command Specification Rev: 1.0
Release Date: 29 May 1997
© 1997 KROHNE Mefltechnik D-47058 Duisburg
Page
23
LANG UNIT
UNIT
CODE
TEXT
TEXT
BYTE #0
BYTE #4
#6
#7
#8
TIME
TIME
UNIT
UNIT
TEXT
TEXT
BYTE #0
BYTE #2
#9
#10
#11
#12
VOLUME
VOLUME
UNIT
UNIT
FACTOR
FACTOR
MSB
MSB
#13
#14
#15
#16
TIME
TIME
UNIT
UNIT
FACTOR
FACTOR
MSB
LSB
Data Byte #0
Language:
0 - Gr.Britain/USA
1 - German
2 - French
3 - Purchased
Data Byte #1-#5
ASCII-text, specifying volume unit. Say, for US barrels liquid it can be ìUSBalî.
Data Byte #6-#8
ASCII-text, specifying time unit. Say, for minutes it can be ìminî.
Data Byte #9-#12
Scaling factor for volume unit, relative to cubic meters, IEEE 754. Say, for US barrels liquid
it will be 8.36364.
Data Byte #13-#16
Scaling factor for time unit, relative to seconds, IEEE 754. Say, for minutes it will be 60.
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-127
Undefined
8.18
Command #149
Write Language And User-Defined Unit
Writes data defining user-created unit, and language that is used for text presentation on the local screen of the
instrument.
REQUEST DATA BYTES
#0
#1
...
#5
DISPLAY
VOLUME
VOLUME
LANG UNIT
UNIT
CODE
TEXT
TEXT
BYTE #0
BYTE #4
#6
#7
#8
TIME
TIME
UNIT
UNIT
TEXT
TEXT
BYTE #0
BYTE #2