KROHNE IFC 010 Converter HART User Manual
Page 20
HARTÆ Communications Protocol
IFC010 Command Specification Rev: 1.0
Release Date: 29 May 1997
© 1997 KROHNE Mefltechnik D-47058 Duisburg
Page
20
Data Byte #2-#5
Pulse value per volume or time unit, depending on PulseType value, IEEE 754. Meaningful
only for ìPulse/Volumeî or ìPulse/Timeî settings of PulseType. The related unit is based on
Primary Variable Unit.
For more details refer to the previous section, 8.11.
CAUTION: PulseWidth should be changed only if the PulseType value is requested either as ìPulse/Volumeî or as
ìPulse/Timeî!
NOTE: The requested PulseWidth value will be set to the nearest possible value within allowed set {5, 10, 20, 50}. If
necessary, PulseValue will be set to the nearest possible value for a given PulseWidth. Master will be prompted about
PulseValue corrections via warning-type response codes.
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1
Undefined
2
Invalid Selection (of PulseType)
3-4
Undefined
5
Too Few Data Bytes Received
6
Undefined
7
In Write Protect Mode
8
Update Failure
9-111
Undefined
112
Pulse Value Exceeded Max and Was Corrected
113
Pulse Value Surpassed Min and Was Corrected
114-127
Undefined
8.13
Command #144
Read Indication Function And Tripping Point
Reads the function of the status indication output and tripping point.
REQUEST DATA BYTES
NONE
RESPONSE DATA BYTES
#0
#1
#2
STATUS
TRIPPING
TRIPPING
INDICATION
POINT
POINT
FUNCTION
MSB
LSB
CODE
Data Byte #0
The function of the status binary output:
0 - All Errors,
1 - Fatal Error,
2 - Off,
3 - On,
4 - Forward/Reverse Indication,
5 - Tripping Point.
Data Byte #1-#2
Tripping point, unsigned integer, in 1/100% of the Primary Variable Upper Range Value
(say, 5% will result in a value of 500 on a bus). The responded value is actually used by the
instrument only when Data Byte #0 is set to ìTripping Pointî.
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-127
Undefined