HARTÆ Communications Protocol
IFC010 Command Specification Rev: 1.0
Release Date: 29 May 1997
© 1997 KROHNE Mefltechnik D-47058 Duisburg
Page
15
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-2
Undefined
3
Passed Parameter too Large
4
Passed Parameter too Small
5
Too Few Data Bytes Received
6
Undefined
7
In Write Protect Mode
8
Update Failure
9-113
Undefined
114
Range Exceeded Max and Was Corrected
115
Range Surpassed Min and Was Corrected
116
Both Range and Pulse Value Corrected
117-127
Undefined
8.5
Command #134
Read Low Flow Cutoff Control And Values
Reads low flow cutoff parameters (Menu 1.3).
REQUEST DATA BYTES
NONE
RESPONSE DATA BYTES
#0
#1
#2
CUTOFF
CUTOFF
CUTOFF
CONTROL
ON
OFF
VALUE
VALUE
Data Byte #0
Cutoff control variable:
0 - cutoff option is switched Off
1 - cutoff option is switched On
Data Byte #1
Cutoff On Value, in 1/10% of the Primary Variable Upper Range Value (say, 5% will result
in a value of 50 on a bus). When cutoff is switched Off (Data Byte #0 = 0), the instrument
still uses the cutoff option, and the defaulted On Value is returned (that is not stored in
EEPROM!). The latter might be either 0.1% or 1% depending on the PulseType value (refer
to the instrument Operating Instructions.
Data Byte #2
Cutoff Off Value, in 1/10% of the Primary Variable Upper Range Value. When cutoff is
switched Off (Data Byte #0 = 0), the instrument still uses the cutoff option, and the defaulted
Off Value is returned (that is not stored in EEPROM!). The latter might be either 0.2% or 2%
depending on the PulseType value (refer to the instrument Operating Instructions.
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-127
Undefined
8.6
Command #135
Write Low Flow Cutoff Control And Values
Writes low flow cutoff parameters.
REQUEST DATA BYTES
#0
#1
#2
CUTOFF
CUTOFF
CUTOFF
CONTROL
ON
OFF
VALUE
VALUE