KROHNE IFC 010 Converter HART User Manual
Page 25
HARTÆ Communications Protocol
IFC010 Command Specification Rev: 1.0
Release Date: 29 May 1997
© 1997 KROHNE Mefltechnik D-47058 Duisburg
Page
25
0
No Command-Specific Errors
1
Undefined
2
Invalid Selection (of Language)
3-4
Undefined
5
Too Few Data Bytes Received
6
Undefined
7
In Write Protect Mode
8
Update Failure
9-127
Undefined
8.19
Command #150
Enable/Disable Password Protection
Installs/uninstalls write protection. Two transaction are implemented: Transaction #1 disables write protection, in this
case a correct password must be ìshownî to transmitter. If protection is disabled and device is open for write operations,
any of two transactions can be used to enable factory-set password. Then the contents of Password field for Transaction
#1 is ignored.
TRANSACTION #0
REQUEST DATA BYTES
#0
WRITE
PROT
CODE
RESPONSE DATA BYTES
#0
WRITE
PROT
CODE
TRANSACTION #1
REQUEST DATA BYTES
#0
#1
#2
#3
#4
WRITE
PROT
PROT
PROT
CODE
CODE
CODE
MSB
LSB
RESPONSE DATA BYTES
#0
WRITE
PROT
CODE
Data Byte #0
Write Protect Code, available via Command #15, Read Primary Variable Output Information:
0 - Not Write Protected
1 - Write Protected
Data Byte #1-#4
HART- encrypted password of the instrument, unsigned long. The encoding scheme is as
follows: the ìRightî-key of device keypad is coded by digit м0о, ìEnterî-key - by м1о and
ìUpî-key - by м2о. For example, some arbitrary key combination ìRight-Right-Up-Up-Up-
Right-Enter-Up-Upî will result in 2220122 (leading zeroes are defaulted for password
operations anywhere).
NOTE: Any nonzero value of Write Protect Code will be interpreted by transmitter as a request to enable protection.
COMMAND-SPECIFIC RESPONSE CODES