Section 4 - calibration, 1 general, Table 4-1. calibration summary (continued) – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.2.48 to 3.04 User Manual
Page 129: General -1, Calibration summary -1
BOP-1K 101509
4-1
SECTION 4 - CALIBRATION
4.1
GENERAL
This section contains the calibration instructions for the Power Supply. It is recommended that
the user be familiar with Local Mode operation (PAR.3.2) before calibrating the unit.
A full calibration consist of a voltage calibration and a current calibration. Both voltage and cur-
rent calibrations consist of zero, max and min, and protection limit calibration. In addition, the
control signals required for series and parallel operation of multiple units are also calibrated. It is
recommended that the unit be recalibrated annually.
In order to enter the calibration mode the correct password may be required (see PAR. 3.2.4.4).
If the password has been lost, call the factory and a special password will be provided. During
the calibration, new calibration data is computed which is then stored in the nonvolatile memory.
Calibration of the BOP is performed in one of three ways: locally using the front panel keys
(PAR. 4.4), remotely by sending commands through either the GPIB or RS 232 bus (PAR. 4.3),
or remotely using the graphical interface supplied with the instrument driver available at
www.kepcopower.com/drivers.htm (PAR. 4.4.3). This VISA compliant driver works with many
GPIB cards from suppliers like National Instruments and Hewlett-Packard. These three ways
cannot be combined. Separate calibration procedures are provided for units connected in series
or parallel.
NOTE: During calibration, various circuits of the BOP are verified. If an error occurs during the
verification process, the unit will beep and an error 24(x), Hardware, (see PAR. B.130)
will be placed in the error queue.
TABLE 4-1. CALIBRATION SUMMARY
Type
Step
Reference Type
and Value
Monitored
Parameter
Output Conditions
Notes
VOLTAGE
INTERNAL
1. ZERO
2. POSITIVE
3. NEGATIVE
Internal
Output Voltage
1. 0.0v
2. +Voltage FS
3. –Voltage FS
NO LOAD
AUTOMATIC VM
1. DVM between OUT S
and COM S.
2. Adjust for zero, posi-
tive and negative FS.
VOLTAGE
PROTECTION
1. POSITIVE
2. NEGATIVE
Internal
Output Voltage
1. +Voltage FS
2. –Voltage FS
NO LOAD
AUTOMATIC CM
1. DVM between OUT S
and COM S.
2. Adjust for positive
and negative FS.
VOLTAGE
EXTERNAL
1. ZERO
2. POSITIVE
External:
1. 0.0V
2. +10.0V
(Analog I/O Port,
pin 11 ref to pin 4)
Output Voltage
1. 0.0v
2. –Voltage FS
NO LOAD
AUTOMATIC VM
1. DVM between OUT S
and COM S.
2. Adjust for zero, posi-
tive FS.
VOLTAGE
GAIN
1. ZERO
2. POSITIVE
External:
1. 0.0V
2. +10.0V
(Analog I/O Port
pin 11 ref to 4)
Output Voltage:
1. 0.0V
2. 0.0V
No Load
Automatic VM
1. DVM between OUT S
and COM S
2. Adjust for zero
(both Zero and Posi-
tive).
EXTERNAL
CONTROLS,
SERIES
1. ZERO
2. POSITIVE
External:
1. 0.0V
2. -10.0V
(Par/Ser CTRL-IN
Port, pin 8 ref to 1)
Output Voltage:
1. 0.0V
2. +10.0V
No Load
Automatic VM
1. DVM between OUT S
and COM S
2. Adjust for zero,
+10.0V
3. Calibrate unit for
Slave in Series