Table c-2. ciil error messages, Figure c-7. sta — status command – KEPCO BIT 232F User Manual
Page 57
![background image](/manuals/367864/57/background.png)
BIT 232 022800
C-5
FIGURE C-7. STA — STATUS COMMAND
Syntax:
STA
Function:
Causes power supply to return operating status to controller.
Description:
This operator commands the power supply to report its present operating status. Status is reported in
the form of a message (character string) as defined below. Any catastrophic error conditions (indicated
by * in the table below) which exist will be reported, until the error condition is corrected. As required
by CIIL, all error messages begin with an ASCII “F” (Fault) followed by a 2 digit code, “07” (Halt). The
code that follows (DCSnn) indicates the type of device and the channel number. The next 3 digit code
describes the nature of the fault: “DEV” for device related errors or “MOD” for non-device errors, such
as syntax.
TABLE C-2. CIIL ERROR MESSAGES
ERROR MESSAGE
EXPLANATION
F07 DCSnn DEV Power Loss
The power supply has lost its input power. *
F07 DCSnn DEV Device Turned Off (BOP)
A shutdown occurred due to overvoltage or overcurrent. *
F07 DCSnn DEV Over Temperature
A shutdown occurred due to thermal causes. *
F07 DCSnn DEV Overload
The voltage or current limit point was exceeded. *
F07 DCSnn DEV Voltage Fault
The output voltage is not within limits (voltage mode). *
F07 DCSnn DEV Current Fault
The output current is not within limits (current mode). *
F07 DCSnn DEV Load Path Fault
Open or miswired load or error sense leads detected. *
F07 DCSnn MOD Invalid Command
Improper syntax was used. **
F07 DCSnn DEV Not Ready
The output voltage or current has not settled. **
F07 DCSnn DEV Device Not Present
The specified power supply was not present during power up or
during the last DCL. **
F07 DCSnn DEV Device Not Responding
The power supply has failed to communicate to the controller. **
F07 DCSnn DEV Invalid Voltage Range
The programmed voltage is outside the power supply's range. **
F07 DCSnn DEV Invalid Current Range
The programmed current is outside the power supply's range. **
F07 DCSnn DEV Set Modifier Error
An improper SET command was sent. **
F07 DCSnn DEV Invalid Device ID
The selected channel was not between 1-31. **
*
Catastrophic error
**
Non-Catastrophic error
STA