HT instruments FULLTEST3 User Manual
Page 83

FULLTEST
3
EN - 82
RCD test (RCD)
RCD types / characteristics:
AC, A or B / General, Selective or Delayed
Measurement modes:
x1/2I
N
, x1I
N
, x2I
N
, xKI
N
(K = 4 B type, K=5 AC, A type),
I
(RAMP), AUTO (sequence: x1/2, x1, xK)
Nominal currents:
10, 30, 100, 300, 500, 650 or 1000 mA
Accuracy of test currents (10 mA):
- 10% / + 0% (I
N
/2)
+ 10% / - 0% (I
N
, 2I
N
, KI
N
)
Accuracy of test currents (30
1000 mA): - 5% / + 0% (I
N
/2)
+ 5% / - 0% (I
N
, 2I
N
, KI
N
)
Input voltage range / frequency:
100
265 V / (50 / 60 Hz) ± 0.5 Hz
Contact voltage limits:
25 V or 50 V selectable
Test current polarity:
POSITIVE or NEGATIVE selectable
Test duration (ms) – TT/TN system:
I
N
(mA)
Ч1/2
Ч1
Ч2
ЧK
AUTO
RAMP
G, S, D
G, S, D
G
S
D
G
S
D
G
S
D
G
S
D
10
30
100
AC 1000
1000 200 250 50 150
320
A 1000
1000 200 250 50 150
320
B 1000
1000
200 250
320
300
AC 1000
1000 200 250 50 150
320
A 1000
1000 200 250 50 150
320
B 1000 1000
320
500
AC 1000
1000 200 250 50 150
320
A 1000
1000 200 250 320
B 1000 1000
320
650
AC 1000
1000 200 250 50 150
320
A 1000
1000 200 250 320
B
1000
AC 1000
1000 200 250 320
A 1000 1000
B
Resolution: 1ms, Accuracy:
± (3% rdg + 2 ms)
Mains voltage
U
L/N
,
U
L/PE
:
Display range
(V)
Resolution
(V)
Accuracy
100
265
1 ±
(3%
rdg.)
Input resistance (U
L/N,
U
L/PE
): 450
k
Ramp test:
YES, current range 10
110% of I
N
in steps of 5% of I
N
AUTO TEST:
YES, test steps are as follows:
- t/I
N
/2 (pos. polarity)
- t/I
N
/2 (neg. polarity)
- t/I
N
(pos. polarity)
- t/I
N
(neg. polarity)
- t/5I
N
, (pos. polarity)
- t/5I
N (neg. polarity)