5.7. GLOBAL EARTH RESISTANCE / CONTACT VOLTAGE (RA)

• According to EN 60204-1, the conditions for protection against electric shock in installations with

automatic disconnection of mains voltage are:
• Measurement or evaluation of fault loop impedance and testing the over-current protection device

involved in the fault loop.

• Limit values are shown in the Table 10 of EN 60204-1.

5.7.1. R

A

LIMIT VALUE CALCULATION

The global resistance R

A

should be lower than or equal to U

C LIM

/ I

N

, where limit contact voltage U

C

can be set to 25 or 50 V.

Example: Selected

U

C LIM

= 50 V

Selected

I

N

= 300 mA

R

A LIM

= 166.7

How to select limit contact voltage U

C LIM

:

Press the MENU

SETUPCONTACT VOL. touch-screen keys and select 25 V or 50 V.

5.7.2. R

A

DISPLAY EXPLANATION

Selectable parameter:

I

N

nominal differential current

10, 30, 100, 300, 500, 650 or 1000 mA

Figure 27

: Display with R

A

test result

1 ..... Selected function.
2 ..... Selected limit contact voltage (25 or 50 V).

3 ..... READY message. It is displayed when mains voltage U

L/PE

within 100 ... 265 V is present.

4 ..... Sub-results, mains voltage U

L/PE

at which the measurement was carried out and contact voltage

U

C

at nominal differential current.

5 ..... Measurement screen touch-screen key.

6 ..... I

N

touch-screen key to select nominal differential current. Currently selected value is displayed in

the bottom of the key.

7 ..... Measurement result (in green colour - result OK, in red colour - result not OK).
8 ..... Real time clock (hh.mm.ss).

9 ..... Unit of the test result.
10 ... Measurement result status (symbol

in green colour - result OK, symbol

in red colour - result

not OK).