A.1 main power supply – Fire-Lite MS-2410BC Conventional Control Panel User Manual
Page 54
Battery Calculations
54
Document #50801 Rev.C 12/14/01 P/N 50801:C
A.1
Main Power Supply
The MS-2410BC provides filtered power for operating the fire alarm control panel, operating external devices and
operating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or non-
alarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the power supply.
Be certain to power 4-wire smoke detectors from TB2, Terminals 3 and 4. In Table A-2 , external devices are con-
nected to TB2 only.
TABLE A-2:
Filtered Load in Standby
@24 VDC
.
Device Type
# of
Devices
Current
(amps)
Total Current
(amps)
Main Circuit Board
1
X
0.138
=
0.138
RTB Remote Trouble Buzzer
(1 max.)
X
0.020
=
LED-10IM
(1 max.)
X
0.017
=
4XTMF Module
(1 max.)
X
0.005
=
2-wire Detector Heads
[ ]
X
[ ]
1
1. Refer to the Device Compatibility Document for 2-wire smoke detector standby current.
=
4-wire Detector Heads
[ ]
X
[ ]
1
=
Power Supervision Relays
2
2. Must use compatible listed Power Supervision Relay.
[ ]
X
0.025
=
Current Draw from TB2
(nonalarm
3
)
3. The total standby current must include both the resettable (TB2 Terminals 3 & 4) and nonresettable (TB2
Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified (see Table A-2 ).
=
Sum Column for Standby Load
=
amps