Fire-Lite MS-2410BC Conventional Control Panel User Manual
Page 36
Programming Function
36
Document #50801 Rev.C 12/14/01 P/N 50801:C
2.
Using the numerical keys, enter the Program Mode password and press the Enter key
3.
The 'pointer' will be located at the Zone 1 alarm LED which will be on steady.
4.
The 'cursor' will be located at the Zone 1 trouble LED which will blink and one or more additional zone trou-
ble LEDs may be on steady
5.
Press the Enter key three times to position the 'pointer' at Zone 4 alarm LED, which corresponds to the Super-
visory Alarms program feature
6.
The 'cursor' should be positioned at Zone 1 trouble LED which corresponds to the Zone 9 latching/auto-
resettable option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41. Note that addi-
tional zone trouble LEDs may be on if corresponding options were previously selected.
F
O
Annunc. Trouble
Zone Disabled
Battery Trouble
Ground Fault
NAC Fault
Signal Silence
Supervisory
Trouble
Password
Enter
Zone 1
Alarm LED
Zone 1
Trouble LED
F
O
Annunc. Trouble
Zone Disabled
Battery Trouble
Ground Fault
NAC Fault
Signal Silence
Supervisory
Trouble
Enter Key
Zone 1
Trouble LED
Zone 4
Alarm LED
- 2401B Circuit Board Standoff Placement (1 page)
- 411UDAC Fire Alarm Communicator (84 pages)
- 411UDAC Dig C Digital Communica unicatortor (1 page)
- 411UDAC Communicator Dress Panel (2 pages)
- 411UDAC Communicator Circuit Board & Transformer (2 pages)
- 411UDAC Fire Alarm Communicator Relay (1 page)
- ACC-25/50 Audio Command Center (1 page)
- ACC-25/50DA Distributed Audio Panel (84 pages)
- ACC-25/50ZS (1 page)
- ACM-16ATF Annunciator Modules (68 pages)
- ACM-8RF Control Relay Module (48 pages)
- APS-6RF Auxiliary Power Supply (28 pages)
- B524BI Plug-in Isolator (4 pages)
- B524RB(A) Plug-in Relay Detector Bases (4 pages)
- B310LP Plug-in Base for Addressable Detector (2 pages)
- B350LP Plug-In Base for Addressable Detector (4 pages)
- BB-55 Battery Box (1 page)
- BG-12 Series Manual Pull Stations (4 pages)
- BG-12LA Manual Pull Station (2 pages)
- BG-12LAO Manual Pull Station (2 pages)
- BG-12LO Manual Pull Station (2 pages)
- BG-12LPS Pre-Signal Manual Pull Station (2 pages)
- BG-12LR Agent Release Pull Station (2 pages)
- BG-12LX Addressable Pull Station (2 pages)
- BG-12SL Single Action Pull Station (2 pages)
- Central Station Receiver (1 page)
- CHG-120 Series Addendum - For Connection Of 100 Amp Hour Batteries (2 pages)
- CHG-120F Battery Charger (28 pages)
- CHG-75 Battery Charger (32 pages)
- CHS-6 Chassis (1 page)
- CHS-6 Chassis for BB-6 Cabinet (1 page)
- CMP-2401B Fire Alarm Control Panel (36 pages)
- CP355 Plug-in Addressable Ionization Sensor (2 pages)
- CRF-300 Relay Control Module (2 pages)
- DACT-UD2 Digital Alarm Communicator/Transmitter (52 pages)
- DP-4XF Dress Panel Kit PID (2 pages)
- ECC-50/100 Emergency Command Center (108 pages)
- ECC-50WBU Backup Amplifier (1 page)
- ECC-50DA/E Distributed Audio Amplifiers (26 pages)
- ECC-FFT (1 page)
- FCPS Series Field Charger/Power Supply (48 pages)
- FCPS Series Field Software Change Procedure (2 pages)
- FHSC-RF FIREFIGHTERS HANDSET STORAGE BOX (1 page)
- ECC-FFT Firefighters Telephone (32 pages)
- H350 Addressable Thermal Sensor (2 pages)