2 programmable features and options – Fire-Lite MS-2410BC Conventional Control Panel User Manual
Page 33
Document #50801 Rev. C 12/14/01 P/N 50801:C
33
Programmable Features and Options
3.2
Programmable Features and Options
Table 3-1 lists the MS-2410BC programmable features and the corresponding options available for each feature. In
programming mode, the zone alarm LEDs are used to 'point' to the program feature and the zone trouble LEDs are
used to select the desired option for each feature.
TABLE 3-1:
Programming Features and Options
Zone Alarm LED
Programmable
Features
Zone Trouble LED
Available Options
1
AUTO-SILENCE
1
Disabled - default
2
Five (5) Minutes
3
Ten (10) Minutes
4
Twenty (20) Minutes
2
SILENCEABLE
NACs
1
NAC 1 & NAC 2 Silenceable (LED On) - default
NAC 1 and NAC 2 Nonsilenceable (LED Off)
3
WALKTEST
1
Audible (LED Off) - default
Silent (LED On)
4
SUPERVISORY
ALARM
1
Zone 9 Latching (LED On) - default
Zone 9 Autoresettable (LED Off)
2
Zone 10 Latching (LED On) - default
Zone 10 Autoresettable (LED Off)
3
Zone 9 Supervisory (LED Off) - default
Zone 9 Smoke Zone (LED On)
4
Zone 10 Supervisory (LED Off) - default
Zone 10 Smoke Zone (LED On)
5
Canadian Supervisory Enabled (LED On) - default
Canadian Supervisory Disabled (LED Off)
5
ALARM
VERIFICATION
1
Verify Alarms (LED On)
Do Not Verify Alarms (LED Off) - default
6
AC LOSS DELAY
1
No Delay - default
2
Six (6) Hour Delay
3
Eight (8) Hour Delay
4
Ten (10) Hour Delay
5
Twelve (12) Hour Delay
6
Fourteen (14) Hour Delay
7
Sixteen (16) Hour Delay
8
Eighteen (18) Hour Delay
7
MODULE
SUPERVISION
1
4XTMF Transmitter Module
2
not used
3
LED-10IM (EIA-485) Module
8
ANNUNCIATOR
MAXIMUM
MONITORED
ADDRESS
1
01 - default
2
02
3
03
4
04
5
05
6
06
7
07
8
08
9
09
10
10
9
TROUBLE
REMINDER
1
Disabled (LED Off) - default
Enabled (LED On)
10
future use