Program Features and Options
14.
Press the Down arrow key to position the 'cursor' at the Zone 5 trouble LED which corresponds to the Cana-
dian Supervisory option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41
15.
Press the keypad 3 key (Toggle Option) to disable the Canadian Supervisory option. The cursor should blink
at a 1/10 second On and 9/10 second Off rate. The LED will turn off when the cursor is moved off of it
16.
Press the Enter key to store all of the selected options for the Supervisory Alarms feature and move the
pointer to the next feature
3.5
Program Features and Options
3.5.1 Program Features
There are ten features that are programmable through the MS-2410BC keypad. Table 3-2 lists the programming fea-
tures and the alarm zones which represent each feature.
3.5.2 Programming Options
Each programming feature listed in Table 3-2 has two or more options associated with it. This section describes each
feature and the available options.
TABLE 3-2:
Program Feature Indicated by Alarm Zone
Alarm Zone LED Number (red)
Programming Feature
1
Auto-silence
2
Silenceable NACs
3
Walktest (audible/silent)
4
Supervisory Alarms
5
Alarm Verification
6
AC Loss Delay
7
Option Module Supervision
8
Number of Annunciators
9
Trouble Reminder
10
future use
F
O
Annunc. Trouble
Zone Disabled
Battery Trouble
Ground Fault
NAC Fault
Signal Silence
Supervisory
Trouble
Down Arrow
Key
Zone 5
Trouble LED