Output Circuits
24
Document #50801 Rev.C 12/14/01 P/N 50801:C
2.5
Output Circuits
DC Power Output Connections
.
Notification Appliance Circuits
The MS-2410BC provides two Notification Appliance Circuits standard as Class B. Each circuit is capable of 2.5
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed 3.6 amps with
the standard transformer, 6.6 amps if an optional XRM-24 Transformer is installed. Circuits are supervised.
Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
4-Wire Smoke Detector Power (500 mA) 24
VDC filtered, resettable power for 4-wire
smoke detectors can be obtained from TB2
Terminals 3(-) and 4(+)
FIGURE 2-6:
Auxiliary Power Connections
Nonresettable Power (500 mA) 24 VDC
filtered, nonresettable power can be
obtained from TB2 Terminals 1(-) and 2(+).
4 3 2 1
FIGURE 2-7:
Notification Appliance Circuit Connections
Class B Notification Appliance Circuit (supervised). 4.7K ohm, ½ watt.
P/N: 71252
Polarized Bell
Polarized Bell
Polarized Horn
Polarized Horn
Polarized Horn
Polarized Horn
Dummy Load all unused circuits (P/N: 71245)
Note: Notification Appliance Circuit polarity
shown in alarm state.