beautypg.com

Figure 3.5 operating power connections – Fire-Lite ACC-25/50DAZS Distributed Audio Panel User Manual

Page 38

background image

38

Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

Installation

Operating Power

connected to this circuit and it may not contain any power disconnect devices. A separate Earth
Ground connection must be made to ensure proper panel operation and lightning and transient pro-
tection. Connect the Earth Ground wire (minimum 14 AWG) to one of the transformer mounting
studs. Do not use conduit for the Earth Ground connection since this does not provide reliable pro-
tection.

Secondary Power Source (Batteries)

Observe polarity when connecting the batteries. Connect the battery cable to P11 on the main cir-
cuit board, using the plug-in connector and cable provided. The battery charger is current-limited
and capable of recharging sealed lead acid type batteries (See Figure 3.5 for battery orientation).
The charger shuts off when the system is in alarm. page 72 for calculation of the correct battery rat-
ing.

!

CAUTION:

SULFURIC ACID

BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN
AND EYES, AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID,
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK
IMMEDIATE MEDICAL ATTENTION.

CAU

TI

ON!

HI

G

H

V

O

LT

AG
E

Figure 3.5 Operating Power Connections

ac

25

dap

ow

r.

w

m

f

ACC-ZSM Mounting Bracket

VAC

Hot (black)

Neutral (white)

Ground (green)

Connect Earth Ground
wire to ground stud

black

red

12 VDC battery

12 VDC battery

This manual is related to the following products: