Fire-Lite ACC-25/50DAZS Distributed Audio Panel User Manual
Page 32
32
Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010
Field Programming
Switch SW1 Settings on Optional FC-MGM Module
•
Switch 6, 7 and 8 - used to determine the number of times the voice message will repeat.
SW2 - Record Bypass Switch (on optional FC-MGM Module)
This switch, when placed in the down position, prevents accidental erasure of stored voice mes-
sages. See 'Operating Instructions' on page 52 for additional information.
•UP Position = The stored digital voice message may be overwritten with
a new one.
•Down Position = The stored digital voice message can not be
overwritten (factory default setting).
SWITCH
6
SWITCH
7
SWITCH
8
NUMBER OF TIMES TO REPEAT DIGITAL
VOICE MESSAGE
ON
OFF
OFF
3
OFF
ON
OFF
3
ON
ON
OFF
6 (factory default)
OFF
OFF
ON
8
ON
ON
ON
INFINITE (until FACP trigger is reset)
Table 2.4 Switch Settings for Message Repeat
RECORD
BYPASS
RECORD
BYPASS