beautypg.com

2 s2 and s3 addressing rotary switches, S2 and s3 addressing rotary switches – Fire-Lite ACC-25/50DAZS Distributed Audio Panel User Manual

Page 29

background image

Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010

29

ACC-ZPM Zone Page Module

Field Programming

2.4.2 S2 and S3 Addressing Rotary Switches

Two addressing switches are located at the bottom right of the ACC-ZPM Zone Page Module. The
switches are used to set the EIA-485 address of the ACC-ZPM to allow communication between it
and the ACC-25/50ZS/T. This communication link allows the ACC-25/50ZS/T to control the
speaker circuits.

To set the address, use a small nonconductive flat-blade screw driver to turn the switch dial so the
arrow points to the correct address number. The factory default setting is S3 = 0 and S2 = 1. The
following illustration shows the switches set for address 01 with S3 (Tens) set to 0 and S2 (Ones)
set to 1.

ACC-ZPM Addressing for Style Y (Class B) Audio Circuits

The ACC-ZPMK, which is located in the main ACC-25/50ZS/T Audio Panel, is set to address 01
(as illustrated in Figure 2.3) for communication with the FACP via the ACS link and will control
Style Y (Class B) Audio Zones 1-8. The ACC-ZPM modules located in the ACC-25/50DAZS
Distributed Audio Panels connected to the ACC-25/50ZS/T Audio Panel, must be set to consecu-
tive addresses, starting with address 01, and will control Style Y (Class B) Audio Zones 9-16 and
17-24 as detailed in the following table.

ACC-ZPM Addressing for Style Z (Class A) Audio Circuits

The ACC-ZPMK, which is located in the main ACC-25/50ZS/T Audio Panel, is set to address 01
(as illustrated in Figure 2.3) for communication with the FACP via the ACS link and will control
Style Z (Class A) Audio Zones 1 - 4. The ACC-ZPM modules located in the ACC-25/50DAZS
Distributed Audio Panels connected to the ACC-25/50ZS/T Audio Panel, must be set to consecu-
tive addresses, starting with address 01, and will control Style Z (Class A) Audio Zones 5-8, 9-12,
13-16, 17-20 and 21-24 as detailed in the following table.

Module

Address (S2 & S3)

Style Y (Class B) Audio Zone

ACC-ZPMK

01

1 - 8

ACC-ZPM (1st)

01

9 - 16

ACC-ZPM (2nd)

02

17 - 24

Figure 2.3 ACC-ZPM Addressing Switches

NOTE: Switch SW2 on the ACC-ZSM module is set to Class B on all ACC-ZSM(s). See 'ACC-
ZSM Zone Splitter Module' on page 30.

Module

Address (S2 & S3)

Style Z (Class A) Audio Zone

ACC-ZPMK

01

1 - 4

ACC-ZPM (1st)

01

5 - 8

ACC-ZPM (2nd)

02

9 - 12

ACC-ZPM (3rd)

03

13 - 16

ACC-ZPM (4th)

04

17 - 20

ACC-ZPM (5th)

05

21 - 24

NOTE: Switch SW2 on the ACC-ZSM module is set to Class A on all ACC-ZSM(s). See 'ACC-
ZSM Zone Splitter Module' on page 30.

This manual is related to the following products: