Maintenance

Note:

Do not change the factory-applied finishes.

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

Specifications


Operating voltage

16 to 33 VDC; 16 to 33 VFWR

Operating current

16 to 33 VDC

16 to 33 VFWR


85 mA
105 mA

Sound output

See Table 3 and Table 4

Synchronization

Pulses at temporal rate within 200 ms on
common circuit for 30 minutes

Horn temporal pattern

0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s
on, 1.5 s off, repeat cycle

Wire size

12 to 18 AWG (0.75 to 2.50 mm²)

Compatible electrical
boxes

2-1/2 in.(64 mm) deep double-gang;
Standard 4 in. square box 2-1/8 in. (54 mm)
deep; surface or weatherproof mounting box
per Table 1

Operating temperature
Indoor
UL

outdoor

ULC

outdoor


32 to 120°F (0 to 49°C)
−31 to 150°F (−35 to 66°C)
−40 to 150°F (−40 to 66°C)

Relative humidity
Indoor
Outdoor


93% noncondensing
98% noncondensing

Table 3: Reverberant room sound output (dBA) [1]

Method Temporal

Continuous

Low

High

Low

High

UL464 at 16 VDC

73

80

77

83

ULI at 24 VDC

77

83

82

86

ULI at 33 VDC

78

85

82

88

[1] Sound level output at 10 ft. (3.05 m)

Table 4: ULC anechoic room sound output (dBA) [1]

Method Temporal

Continuous

Low

High

Low

High

16 to 33 VDC

93

98

86

91

16 to 33 VFWR

96

100

90

93

[1] Average peak sound level output at 10 ft. (3.05 m)

Meets or exceeds CAN/ULC-S525-07, 85 dBA minimum anechoic at 3
meters, all settings

Table 5: ULC directional characteristic

Angle dBA

90° 0

(ref)

57° and 123°

−3

37° and 143°

−6

Note: Horizontal and vertical axes provide the same pattern.

Regulatory information


Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the date code (located on
the product identification label) are the year of
manufacture.

UL/ULC rating

Regulated 24 DC and Regulated 24 FWR [1]

Environmental
class

Indoor or outdoor

North American
standards

Meets: UL 464 and CAN/ULC-S525-07

Follow: NFPA 72 and CAN/ULC-S524

2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.

[1] This device was tested to the regulated 24 DC/FWR operating
voltage limits of 16 V and 33 V.

Contact information

For contact information, see www.utcfireandsecurity.com.