Aux contacts – Edwards Signaling INT-03 Series User Manual
Page 4
Ordering/Electrical Specifications
General Specifications
UL/CSA/TUV
CSA submitted
Weight:
INT-03-24:
9 oz.
INT-03-120/230:
15 oz.
Field wiring size
12 gauge max.
Temperature range
32
°
F to 149
°
F (-0
°
C to 65
°
C)
Relative humidity
30 to 95% non-condensing
Power Supply (+, - or L1, L2)
INT-03-024
24 VDC +/- 15% 100m
Required Fuse:
1/4A (250V, 5x20mm, F/T)
INT-03-120
120 VAC +10% -20%, 5VA, 50/60 Hz
Required Fuse:
80mA (250V, 5x20mm, F/T)
Control Inputs (X1, X2 & Y1, Y2 terminals)
Open-circuit voltage
24VDC
Closed-circuit current
24mA
Max. contact resistance
30 Ohms
Simultaneity
500 ms typical
Safe Outputs (A,B/C,D terminals)
Voltage
230 VAC/60VDC
Current
4A (resistive) each output
Resonse time
< 100 ms
Fuse
4A, 250V, 5 x 20 mm
AUX. Signaling Outputs (E,F,G terminals)
Voltage
120 VAC/30VDC
Current
1A (resistive)
Note: Transient protection is required across the load when switching an
inductive load.
PART NUMBER
POWER INPUT (L1.L2)
INPUT FUSE REQUIRED
INT-03-024
24VDC +/-20%
Fast acting 1/4A (250V, 5 x 20mm, F/T)
INT-03-120
120VAC +10%, -20%, 50/60 Hz, 5VA
Fast acting 80mA (250V, 5 x 20mm, F/T)
European Directives
Machinery Directive (98/37/EEC)
Low Voltage Directive (73/23/EEC), LVD
Specific European Standards
EN60204-1 Safety of electrical equipment of industrial
machines: 1993
EN954-1 Risk Assessment Category 4 depending on wiring
method, See diagrams: 1997
EN50081-2 Electromagnetic Emissions: 1995
EN50082-2 Electromagnetic Immunity: 1995
IEC 664-1 Insulation requirements: 1992
IEC 68, part 2-1, 2-2, 2-3, 2-6, 2-14, 2-27, 2-30.
EN1760-1:1998
File E 122942
Power
Guards
E,G
F,G
Off
Open or Closed
Closed
Open
On
Closed
Closed
Open
On
Open
Open
Closed
Declaration of Conformity
available upon request.
AUX Contacts