Aux contacts – Edwards Signaling INT-03 Series User Manual

Page 4

background image

Ordering/Electrical Specifications

General Specifications

UL/CSA/TUV

CSA submitted

Weight:

INT-03-24:

9 oz.

INT-03-120/230:

15 oz.

Field wiring size

12 gauge max.

Temperature range

32

°

F to 149

°

F (-0

°

C to 65

°

C)

Relative humidity

30 to 95% non-condensing

Power Supply (+, - or L1, L2)

INT-03-024

24 VDC +/- 15% 100m

Required Fuse:

1/4A (250V, 5x20mm, F/T)

INT-03-120

120 VAC +10% -20%, 5VA, 50/60 Hz

Required Fuse:

80mA (250V, 5x20mm, F/T)

Control Inputs (X1, X2 & Y1, Y2 terminals)

Open-circuit voltage

24VDC

Closed-circuit current

24mA

Max. contact resistance

30 Ohms

Simultaneity

500 ms typical

Safe Outputs (A,B/C,D terminals)

Voltage

230 VAC/60VDC

Current

4A (resistive) each output

Resonse time

< 100 ms

Fuse

4A, 250V, 5 x 20 mm

AUX. Signaling Outputs (E,F,G terminals)

Voltage

120 VAC/30VDC

Current

1A (resistive)

Note: Transient protection is required across the load when switching an
inductive load.

PART NUMBER

POWER INPUT (L1.L2)

INPUT FUSE REQUIRED

INT-03-024

24VDC +/-20%

Fast acting 1/4A (250V, 5 x 20mm, F/T)

INT-03-120

120VAC +10%, -20%, 50/60 Hz, 5VA

Fast acting 80mA (250V, 5 x 20mm, F/T)

European Directives
Machinery Directive (98/37/EEC)
Low Voltage Directive (73/23/EEC), LVD

Specific European Standards
EN60204-1 Safety of electrical equipment of industrial
machines: 1993
EN954-1 Risk Assessment Category 4 depending on wiring
method, See diagrams: 1997
EN50081-2 Electromagnetic Emissions: 1995
EN50082-2 Electromagnetic Immunity: 1995
IEC 664-1 Insulation requirements: 1992
IEC 68, part 2-1, 2-2, 2-3, 2-6, 2-14, 2-27, 2-30.
EN1760-1:1998

File E 122942

Power

Guards

E,G

F,G

Off

Open or Closed

Closed

Open

On

Closed

Closed

Open

On

Open

Open

Closed

Declaration of Conformity

available upon request.

AUX Contacts